SYx-P Interface Wiring Detail
Potentiometer
(Factory Pre-set)
For 2-position actuators with 1k feedback option
Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
When a valve is closed: 8, 9 1k Ω
9, 10 0k Ω
When a valve is opened: 8, 9 0k Ω
9, 10 1k Ω
For modulating actuators with 1k feedback option*
Potentiometer points 1, 2, 3 are wired to terminal blocks 8, 9, 10.
When a valve is closed: 8, 9 1k Ω
9, 10 0k Ω
When a valve is opened: 8, 9 0k Ω
9, 10 1k Ω
INPUT = 2-10 VDC
INPUT = 4-20mA
INPUT = 1-5 VDC
OUTPUT = 2-10 VDC
OUTPUT = 4-20mA
LOSS OF SIGNAL = STOP
RESPONSE = REVERSE
RESPONSE = DIRECT
LOSS OF SIGNAL = CLOSED
(Direct Acting)
LOSS OF SIGNAL = OPEN
(Reverse Acting)
LOSS OF SIGNAL = OPEN
(Direct Acting)
LOSS OF SIGNAL = CLOSED
(Reverse Acting)
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
12345678
6782354 1
876 24531
876 24531
876 24531
6782354 1
876 24531
78564231
876 24531
876 24531
Notes:
1. Do not change sensitivity or dip switch settings with power applied!
2. VR1 and VR2 are factory calibrated and should not be moved.
3. Motor CAMS have been factory calibrated and should not be moved.
Dip
Switch
Settings
Sensitivity switch s etting
is position #3 for factory
default. To widen dead-
band, select a higher
number (up to 9).
WARNING
*On modulating
actuators DO NOT
master/slave using
optional potentiometer.
INSTALLATION NOTES
CAUTION
LED Close
LED Open
N Power Supply (3)
+ Power Supply (4)
Control Signal (5)
Control Signal (6)
Feedback (11)
Feedback (12)
VR1
VR2
Sensitivity