100 to 240 VAC
a open
a closed
The indication of direction
is valid for switch position 1.
Blu (1) Common
Blk (2) +
Wht (3) +
a
N L1
H L2
–
10
2
100 to 240 VAC
The indication of direction
is valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
N L1
H L2
10
On/Off
Floating Point
Actuators:
LMX120-3 AMX120-3 LRX120-3 CMB120-3
NMX120-3 GMX120-3 ARX120-3
15
19
LMB(X), NMB(X), AMB(X), GMB(X), LRB(X), and ARB(X)
can be supplied with either 120 VAC or 230 VAC.
All 120VAC and 230VAC actuators use appliance rated
cables.
Meets cULus requirements without the need of an
electrical ground connection.
INSTALLATION NOTES
APPLICATION NOTES
Equipment damage!
Actuators may be connected in parallel. Power
consumption and input impedance must be observed.
2
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
19 19
Actuators with appliance cables are numbered.
A
W364_11
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Wiring for Damper Actuators and Control Valves
On/Off and Floating Point, Non-Spring Return, 100 to 240V
Refer to page 26 for auxiliary switch (-S models) wiring.